Measuring range |
0.00-20.00? |
Open circuit voltage |
5V±0.4V DC |
Measuring current |
200mA DC(nominal value) |
Accuracy |
±3%rdg±5dgt |
Display range |
30V-270V |
Accuracy |
±5V |
Protective conductor resistance test |
|
Measuring range |
0.00-20.00? |
Open circuit voltage |
5V±0.4V DC |
Measuring current |
200mA DC(nominal value) |
Accuracy |
±3%rdg±5dgt |
Insulation resistance test |
|
Rated volatge |
250V, 500V |
Measuring range |
0.00-20.00M? |
No-load voltage |
250V DC +20%,-0%, 500V DC +20%,-0% |
Short circuit current |
1.5mA DC or less |
Accuracy |
±2%rdg±3dgt |
Load current/Leakage current test |
|
Item |
Load current, Leakage current |
Mains voltage range |
100-253V/50Hz |
Measuring range |
0.10-10.00A rms, 0.10-20.00mA rms |
Accuracy |
±10%rdg±5dgt, ±3%rdg±5dgt |
RCD test |
|
Rated voltage |
230V -15% - +10%/50Hz |
Rated current |
10mA/30mA |
Function |
× 1, × 5 |
Test duration |
0.0ms-500.0ms, 0.0ms-40.0ms |
Operating time accuracy |
±2ms(?40ms),±8ms(>40ms) |
General |
|
Power source |
LR6(AA)(1.5V) × 6 |
Applicable Standards |
IEC/EN61010-1 CAT II 300V, IEC/EN61010-2-030, IEC/EN61010-031, EN61326-2-2, AS/NZ3760 |
Dimensions / Weight |
261(L) × 104(W) × 57(D)mm / Approx. 930g(including batteries) |
Included Accessories |
7277(Mains lead), 7129A(Test lead with Alligator clip), 7161A(Flat test prod), 7276(Adaptor for Extension cord), 9193(Carrying case), 8928(Fuse[10A/250V]), 9121(Shoulder strap), Buckle, LR6(AA) x 6, Instruction manual |
Optional Accessories |
8263-USB(USB cable with "KEW Report(software)"), 7275(Printer cable:Mini Din 6pin-D-sub 9pin), 7248(Test lead with Alligator clip and Flat test probe) |