Power Clamp meter
Model No: KEW 2060BT

Catalogue

KEW 2060BT - Clamp Power Meter

  • Conductor size ?75mm and busbar of 80×30mm or less
  • Current up to 1000A rms
  • Voltage up to 1000V rms
  • Harmonics up to 30th
  • Phase rotation
  • Bluetooth communication functions

Wiring connections

1P2W, 1P3W, 3P3W, 3P4W

Measurements and parameters

Voltage, Current, Frequency, Active power, Reactive power, Apparent power, Power factor(cos?), Phase angle, Harmonics(THD-R/THD-F), Phase rotation

AC Voltage

Range

1000V

Accuracy

±0.7%rdg±3dgt (40.0~70.0Hz) ±0.3%rdg±5dgt (70.1~1KHz)

Crest factor

1.7 or less

AC Current

Range

40.00/400.0/1000A (Auto-ranging)

Accuracy

±1.0?rdg±3dgt (40.0~70.0Hz) ±2.0?rdg±5dgt (70.1~1kHz)

Crest factor

3 or less on 40.00A/400.0A range, 3 or less 1500A peak on 1000A range

Frequency

Display range

40.0~999.9Hz

Accuracy

±0.3?rdg±3dgt

Active power

Range

40.00/400.0/1000kW (Auto-ranging)

Accuracy

±1.7%rdg±5dgt (PF1, sine wave, 45?65Hz) influence of phase angle within ±3.0°

Apparent power

Range

40.00/400.0/1000kVA (Auto-ranging)

Reactive power

Range

40.00/400.0/1000kVar (Auto-ranging)

Power factor

Display range

-1.000~0.000~1.000

Phase angle(1P2W only)

Display range

180.0~0.0~+179.9

Harmonics RMS *Content rate

Analysis order

1st~30th order

Effective frequency

50/60Hz

Accuracy

±5.0?rdg±10dgt (1~10th) ±10?rdg±10dgt (11~20th) ±20?rdg±10dgt (21~30th)

Harmonics THD-R/THD-F

Display range

0.0%?100.0%

Accuracy

±1 against the calculated results of each measured value

Phase rotation

ACV 80~1100V (45~65Hz)

Other functions

MAX/MIN/AVG/PEAK, Data hold, Back light, Auto power off

General

Communication interface

Bluetooth®5.0, Android™5.0 or more, iOS 10.0 or more ?1

Power source

LR6 (AA) (1.5V) ×2

Continuous measuring time

Approx. 58 hours

Conductor size

?75 mm (max) and busbar of 80 × 30 mm or less

Dimensions / Weight

283(L) × 143(W) × 50(D) mm / Approx. 590g (including batteries)

Applicable Standards

IEC 61010-1, IEC 61010-2-032 (main unit) / IEC 61010-031 (test leads) CAT IV 600 V / CAT III 1000 V Pollution degree 2, IEC 61326 (EMC) Class B, EN50581 (RoHS), EN 301 489-1, EN 300 328, EN 62479, IEC 60529 (IP40)

Included Accessories

7290 (Test leads) 9198 (Soft Case) LR6(AA)×2, Instruction Manual