Multi Function Tester
Model No: KEW 6516BT

Catalogue

KEW 6516BT - Multi Function Tester

  • Color LCD 3.5 inches dot matrix.
  • Anti-Trip Technology (with 2 & 3 wire) for no trip LOOP L-PE testing on all RCDs.
  • With 2 wire only, very useful in case of no Neutral (i.e. 3-phase motor lines).
  • High test current range of 2? with 0.001? resolution.
  • Zs Limit compares the values required by Electrical Installations Standard with measured results.
  • Type AC, A, F, B(General & Selective), EV and Variable RCDs.
  • Single and Auto test, Ramp test and Contact voltage.
  • Earth resistance test 2 and 3 wires with all accessories included.
  • Resistance test 100, 250, 500 & 1000V with auto discharge voltage.
  • Continuity test at 200mA or 15mA with selectable buzzer for fast judgment.
  • On 3-phase lines with clear indication of the sequence on the display.
  • TRMS Voltage measurements 2-600V, Mains Frequency.
  • Display shows how to connect the instrument according to the function selected.
  • Surge Protection Device test, for SPD that uses varistor.
  • Portable Appliance Tester function, for Insulation and Protective conductor resistance test Communication by "KEW CONNECT".
  • IEC 61010-1 CAT IV 300 V, CAT III 600 V. IEC 61557-1,2,3,4,5,6,7,10.

Test voltage

100V, 250V, 500V, 1000V, Max.1000V

Measuring ranges

2.000/20.00/200.0M? (Auto-ranging), 20.00/200.0/1000M? (Auto-ranging), 20.00/200.0/2000M? (Auto-ranging), 0-1000V (goes up by 1V)

Accuracy

±2%rdg±6dgt (2.000/20.00M?) ±5%rdg±6dgt (200.0M?) ±2%rdg±6dgt (20.00/200.0M?) ±5%rdg±6dgt (1000M?), ±2%rdg±6dgt (20.00/200.0M?), ±5%rdg±6dgt (2000M?), ±5%rdg±5dgt

Rated current

1.0-1.2mA @0.1M? 1.0-1.2mA @0.25M?, 1.0-1.2mA @0.5M?, 1.0-1.2mA @1M?

Short circuit current

1.5mA max

Loop impedance

Function

LOOP ATT

L-PE/L-N (3wire), L-PE(2wire)

LOOP HIGH

L-PE (0.01?Res), L-PE (0.001?Res) High test current(25A), L-N/L-L

Rated voltage

100-260V (50/60Hz), 48-260V (50/60Hz), 48-260V (50/60Hz), 100-260V (50/60Hz), 48-500V (50/60Hz)

Impedance range

20.00/200.0/2000? (Auto-ranging), 20.00/200.0/ 2000? (Auto-ranging), 2.000?, 20.00?

Accuracy

±3%rdg±6dgt , ±3%rdg±10dgt, ±3%rdg±4dgt, ±3%rdg±25m?, ±3%rdg±4dgt

Nominal test current at 0? external loop: Magnitude/ Duration at 230V

L-N:6A/60ms N-PE:10mA, L-PE:15mA, 20?: 6A/20ms 200?: 0.5A/20ms 2000?: 15mA/500ms, 25A/20ms, 6A/20ms

PSC/PFC

Range

2000A/20kA (L-N(PSC)/ L-PE(PFC)), 2000A/20kA (PFC), 2000A/20kA (PFC), 2000A/50kA (PFC), 2000A/20kA (PSC)

Accuracy

PSC/PFC accuracy is derived from measured loop impedance specification and measured voltage specification

RCD

Rated voltage

100-260V(50/60Hz)

Function

x1/2, x1,x5,Ramp,Auto,Uc , 6/10/30/100/300/500/1000mA/variable

RCD type

AC(G/S), A(G/S), F(G/S), B(G/S), EV

Trip current setting

x1/2, x1,Uc

10/30/100/300/ 500/1000mA(G) 10/30/100, 10/30/100/ 300/500mA/ 300/500(S), 10/30/100/ 300/500mA, 10/30/100/ 300mA, 6mA(x1 only)

x5

10/30/100mA 10/30/100mA, 10/30/100mA, 10/30mA,

Ramp

10/30/100/ 300/500mA 10/30/100/ 300/500mA, 10/30/100/ 300/500mA, 10/30/100/ 300mA, 6mA

Accuracy

Trip current

x1/2

-8% - -2%, -10% - 0%, -10% - 0%, -10% - 0%

x1

+2% - +8%, 0% - +10%, 0% - +10%, 0% - +10%, 0% - +10%

x5

+2% - +8%, 0% - +10%, 0% - +10%, 0% - +10%

Ramp

-4% - +4% -10% - +10%, -10% - +10%, -10% - +10%, -10% - +10%

Trip time

x1/2

2000ms(G/S):±1%rdg±2ms

x1

550ms(G):±1%rdg±2ms,1000ms(S):±1%rdg±2ms, 10.5s:±1%±2?

x5

410ms(G/S):±1%rdg±2ms

Continuity

Range

20.00/200.0/2000? (Auto-ranging)

Open circuit voltage(DC)

7-14V

Measuring current

200mA

>200mA or more(2? or less)

15mA

15mA±3mA(short-circuit)

Accuracy

±2%rdg±8dgt

Volts

Range

300.0/600V(Auto-ranging)

Measuring ranges

Volts

2-600V

Frequency

45-65Hz

Accuracy

Volts

±2%rdg±4dgt

Frequency

±0.5%rdg±2dgt

Phase Rotation

Rated voltage

48-600V(50/60Hz)

Remarks

Remarks Correct phase sequence: are displayed “1.2.3” and mark Reversed phase sequence: are displayed “3.2.1” and mark

Earth

Range

20.00/200.0/2000?(Auto-ranging)

Accuracy

±2%rdg±0.08?(20.00?) ±2%rdg±3dgt(200.0/2000?)

Applicable standards

IEC 61010-1 CAT IV 300V ,CAT III 600 V Pollution degree 2 IEC 61010-2-034 IEC 61557-1,2,3,4,5,6,7,10 IEC 60529(IP40) IEC 61326(EMC)

Power source

LR6 (AA) (1.5V) ×8

Communication interface

USB, Bluetooth®5.0,Android™5.0 or more, iOS 10.0 or more ?1

Dimensions / Weight

136(L) × 235(W) × 114(D) mm / Approx. 1300g (including batteries)

Included Accessories

Main test lead?2 7281(Test leads with remote control switch) 7246(Distribution board test lead) 7228A(Earth resistance test leads) 8041(Auxiliary earth spikes[2 spikes/1 set]) 9084(Soft case) 9142(Carrying case) 9151(Shoulder strap) 9199(Shoulder pad) LR6(AA) × 8, Instruction manual, Calibration certificate

Optional Accessories

8212-USB(USB adaptor with "KEW Report(Software)'') 8259(Adapter for measurement terminal) 7272(Precision measurement Cord set) 8017A(Extension prod long)
No datas found