Power Analyser up to 4ch
Model No: PW3390

Catalogue

Hioki benchtop power meters and power analyzers are best in class power measuring instruments for measuring single to three-phase lines with a high degree of precision and accuracy. The PW3390 is a high-precision, broad-range power analyzer for measuring electrical power from DC to inverter frequencies, providing four input channels to support single- and three-phase inverter motor systems up to 4000 A AC/DC with superior accuracy.
High-accuracy, high-speed calculation of transient-state power in 50 ms; harmonic analysis; display of instantaneous waveforms; noise analysis; and simultaneous parallel calculation of all parameters, including efficiency loss

Harmonic measurement

Input: 4 ch, Synchronization frequency range: 0.5 Hz to 5 kHz, Number of harmonic orders: Max. 100th order

Noise measurement

Number of channels: 1 ch (select one channel from CH1 to CH4), Maximum analysis frequency: 200 k/ 50 k/ 20 k/ 10 k/ 5 k/ 2 kHz

Motor Analysis (PW3390-03 only)

Input: 3 ch (CH A, CH B, CH Z), Measurement parameters: Voltage, torque, rotation rate, frequency, slip, and motor power

Measurement range

Voltage range: 15 to 1500 V, 7 ranges Current range: 0.1 A to 20 kA (depends on current sensor)

Synchronization frequency range

0.5 Hz to 5 kHz

Measurement line type

Single-phase 2-wire, single-phase 3-wire, three-phase 3-wire, three-phase 4-wire, Voltage 4 channels, Current 4 channels, Isolated between each channel

Measurement items

PW3390-03 only: Torque, Rotation, Frequency, Slip, or Motor power

Effective measuring power range

0.0150 W to 39.600 MW (determined automatically by the combination of voltage range, current range, and measurement line)

Basic accuracy (45 to 66 Hz)

Voltage: ±0.04 % rdg. ±0.05 % f.s. Current: ±0.04 % rdg. ±0.05 % f.s. Active power: ±0.04 % rdg. ±0.05 % f.s.

Frequency band

DC, 0.5 Hz to 200 kHz

Data update rate

50 ms (For harmonic/frequency measurement, depends on the synchronization frequency when less than 45 Hz)

Display refresh rate

200 ms (Independent of internal data update rate; waveform and FFT depend on the screen)

Auto-Save Functions

Each value is stored to CF card during every measurement interval (not available for USB storage), OFF, 50 msec to 500 msec, 1 sec to 30 sec, 1 minute to 60 minutes, 15 settings

External interfaces

LAN, USB (for communication/ memory), RS-232C (for communication/LR8410 link), CF card, Synchronization control, External Control

Logger connectivity

Sends measured values wirelessly to logger by using a BluetoothⓇ wireless technology serial conversion adapter. (Supported devices: Hioki LR8410 Link-compatible loggers)

Power supply

100 to 240 V AC, 50/60 Hz, 140 VA max.

Dimensions and mass

340 mm (13.39 in)W × 170 mm (6.69 in)H × 156 mm (6.14 in)D, 4.6 kg (162.3 oz)

Included accessories

Instruction Manual ×1, Power cord ×1, Measurement Guide ×1, USB cable ×1, Input cord label ×2, D-sub connector × 1 (PW3390-02, PW3390-03)